Thông số kỹ thuật

  • Chế độ điều khiển:1: V/F, 2: SVC, 3: PM.
  • Tiêu chuẩn: IP20/IP00.
  • Tần số ngõ ra: 0 – 599Hz.
  • Khả năng quá tải: 120% of rated current for 1 minute during every 5 minutes.
  • Hàm bảo vệ: Protection Characteristics Over-current Protection For drive model 230V/460V: Over-current protection: 200% rated current for light duty; 240% rated current for normal duty Current clamp:『 Light duty: 130–135%』 ;『 Normal duty: 170–175%』 For drive model 575/690V: Over-current protection: 225% rated current for normal duty Current clamp:『 Light duty: 128–141%』 ;『 Normal duty: 170–175%』 Over-voltage Protection 230V models: drive will stop when DC bus voltage exceeds 410V 460V models: drive will stop when DC bus voltage exceeds 820V 575V models: drive will stop when DC bus voltage exceeds 1016V 690V models: drive will stop when DC bus voltage exceeds 1189V Over-temperature Protection Built-in temperature sensor Stall Prevention Stall prevention during acceleration, deceleration and running independently Restart After Instantaneous Power Failure Parameter setting up to 20 seconds Grounding Leakage Current Protection Leakage current is higher than 50% of rated current of the AC motor drive Short-circuit Current Rating (SCCR) Per UL508C, the drive is suitable for use on a circuit capable of delivering not more than 100 kA symmetrical amperes (rms) when protected by fuses given in the fuse table..

Dải công suất điện áp

  • 3- pha 200-220V: 0.75- 90kW
  • 3-phase 380-400V: 0.75- 630kW

Ý nghĩa mã hàng

Ví dụ: VFD1850CP43A-00

  • VFD ký hiệu tên dòng biến tần của hãng Delta.
  • 1850 ứng với công suất định mức 185kW.
  • CP ký hiệu dòng Delta CP2000.
  • 43 điện áp ngõ vào 3 pha 380-400V ngõ ra 3 pha 380-400V.

Dịch vụ

  • Hỗ trợ kỹ thuật, hướng dẫn đấu nối, cài đặt thông số.
  • Chuẩn đoán lỗi, sửa chữa hư hỏng.

Tham khảo: Tài liệu đấu dây cài đặt mã lỗi biến tần Delta CP2000

0
Nếu có thắc mắc hoặc đóng góp vui lòng gửi bình luận.x